Govur University Logo
--> --> --> -->
...

How does a modulating burner in a boiler system adjust its firing rate, and what sensors provide the necessary feedback?



A modulating burner in a boiler system adjusts its firing rate – the amount of fuel it burns – to precisely match the heating demand. This adjustment is achieved through a control system that varies the fuel and air supply to the burner. The control system is driven by feedback from several sensors that monitor key operating parameters. One of the most critical sensors is the water temperature sensor (or steam pressure sensor in steam boilers). This sensor continuously monitors the temperature of the water (or the pressure of the steam) being produced by the boiler. As the heating demand changes, the water temperature (or steam pressure) will fluctuate. If the temperature (or pressure) drops, indicating an increased demand for heat, the control system will increase the firing rate. Conversely, if the temperature (or pressure) rises, indicating a reduced demand for heat, the control system will decrease the firing rate. Another important sensor is the oxygen (O2) sensor in the flue gas. This sensor measures the amount of oxygen present in the exhaust gases produced by the combustion process. This information is used to optimize the air-fuel ratio, ensuring efficient combustion and minimizing emissions. The control system adjusts the air supply to the burner based on the O2 sensor reading. If the O2 level is too high, it indicates that there is too much air and the burner is running inefficiently. If the O2 level is too low, it indicates that there is not enough air and the burner is producing excessive carbon monoxide (CO). Some advanced systems also use a carbon monoxide (CO) sensor directly to ensure complete combustion and minimize harmful emissions. The control system uses the feedback from these sensors to continuously adjust the fuel and air supply to the burner, maintaining optimal efficiency and meeting the heating demand.