Explain the significance of electrical area classification in environments with flammable gases and describe how these classifications determine the appropriate selection and installation of electrical equipment.



Electrical area classification is of paramount significance in environments where flammable gases are present because it dictates the appropriate selection and installation of electrical equipment to prevent ignition of the flammable atmosphere, thus minimizing the risk of explosions and fires. This classification system is based on the probability of a flammable atmosphere being present and helps ensure the safety of personnel and facilities. Electrical equipment that can create a source of ignition (like sparks or high surface temperatures) must be selected and installed based on this area classification.

The classification system typically divides hazardous locations into different zones or divisions based on the frequency and duration of the presence of a flammable atmosphere. The specifics of the classifications can vary slightly depending on the particular standard being applied (such as the IEC or NEC standards), but the general principles are largely consistent.

For instance, under the IEC standards, hazardous areas are classified into Zones 0, 1, and 2. Zone 0 is an area where a flammable atmosphere is present continuously or for long periods, such as inside a storage tank containing flammable liquid or in the immediate vicinity of a persistent gas leak. Zone 1 is an area where a flammable atmosphere is likely to occur occasionally in normal operations, such as around a pump handling flammable liquids or near a pressure relief valve. Zone 2 is an area where a flammable atmosphere is likely to occur only under abnormal conditions, such as in the area surrounding a processing plant where a leak is possible, but not normally present.

In contrast, under the NEC (National Electrical Code) system used in North America, the classes are divided into Class I, II, and III, with divisions 1 and 2 within each class. Class I refers to locations where flammable gases or vapors are present, while Class II refers to locations where combustible dust is present, and Class III refers to locations with ignitable fibers or flyings. Class I Division 1 is equivalent to IEC Zone 0 and Zone 1 where flammable gases are expected to be present during normal operations. Class I Division 2 is equivalent to IEC Zone 2 where gases are present in abnormal situations.

The electrical equipment to be installed within a classified area must be specifically designed and tested to not cause an ignition of a flammable atmosphere present. This is where the area classification is most important. Different equipment construction techniques, such as explosion-proof, intrinsically safe, purged, and non-incendive are used. For example, in a Zone 0 area, electrical equipment must be intrinsically safe, meaning it will not create sparks or have hot surfaces that could trigger ignition even if the gas enters the device housing. This equipment has a very low energy output that cannot ignite a flammable mixture. Another method is to completely encapsulate the electrical component, which prevents the flammable gas from reaching the electrical component. In a Zone 1 area, explosion-proof equipment, which is designed to contain any potential explosion within its housing, is permissible. The enclosure itself is built to contain an internal explosion and also to not have hot surfaces that will ignite the flammable gas. In Zone 2 areas, equipment that is non-incendive, such as purged enclosures or sealed devices, can be used. These devices are designed to not produce enough energy to ignite a flammable atmosphere.

For example, a common practical scenario would be a gas metering station that is typically designated a Zone 1 or Division 1 location due to the possibility of leaks. In this area, an intrinsically safe or explosion-proof gas detector would be installed along with explosion-proof junction boxes and wiring practices. A Zone 2 area may be considered the perimeter of the station or an adjacent control room where flammable gases are unlikely to be present but could be possible, where non-incendive equipment would be used. Another example would be inside a spray booth where paints and solvents with flammable vapors are present during normal operations. Within the spray booth, equipment will need to be rated for Zone 1 or Division 1, and this means that electrical motors, lights, and control panels must be explosion-proof. In summary, electrical area classification is a crucial aspect of safety engineering in hazardous locations, providing guidelines for the appropriate selection and installation of electrical equipment to prevent ignition. Equipment must be certified and rated for the designated zone or class to ensure it can operate safely in the presence of flammable gases.