Govur University Logo
--> --> --> -->
...

Explain the process of performing a dielectric withstand test (hi-pot test) on a distribution cable and interpreting the results.



A dielectric withstand test, also known as a hi-pot test, is performed on distribution cables to verify the integrity of their insulation. It involves applying a high-voltage AC or DC signal to the cable and measuring the leakage current. The process starts with isolating the cable from the system and ensuring it is de-energized. Proper Lockout/Tagout (LOTO) procedures must be followed. The cable should be visually inspected for any signs of damage. The hi-pot tester is then connected between the conductor and the shield or ground. The test voltage is gradually increased to a specified test level, typically several times the cable's normal operating voltage. This test voltage is maintained for a specified duration, typically one minute. During the test, the leakage current is monitored. A small leakage current is normal, but a sudden increase or a sustained high leakage current indicates a weakness in the insulation. If the cable withstands the test voltage for the specified duration without breakdown, it passes the test. If the cable breaks down, meaning the insulation fails and a large current flows, the test is stopped immediately, and the cable fails the test. Interpretation of the results involves analyzing the leakage current. A gradual increase in leakage current may indicate insulation degradation. A sudden jump in leakage current indicates a more severe insulation defect. A high leakage current throughout the test indicates widespread insulation damage. The test results should be compared to previous test results and industry standards to assess the cable's condition. Cables that fail the hi-pot test should be replaced to prevent future failures.