Govur University Logo
--> --> --> -->
...

In a delta-connected system, how is a ground fault detected without a neutral connection?



In a delta-connected system, there is no direct neutral point to connect to ground, which makes ground fault detection more challenging than in wye-connected systems with a grounded neutral. Several methods are used to detect ground faults in delta systems. One common method is to use a ground fault relay that monitors the zero-sequence current. Although there is no physical neutral, a zero-sequence current can still flow during a ground fault due to the capacitance to ground of the system conductors. A grounding transformer, such as a zig-zag transformer or a wye-delta transformer, can be used to create an artificial neutral point. The zero-sequence current will then flow through this artificial neutral, allowing it to be detected by the ground fault relay. Another method is to use a residual voltage relay. During a ground fault, the voltages to ground on the unfaulted phases will increase. The residual voltage is the sum of the three phase-to-ground voltages, which should be zero under normal conditions. A residual voltage relay monitors this voltage and trips if it exceeds a certain threshold. Broken delta voltage transformers can also be used. Three single-phase voltage transformers are connected in an open-delta configuration. Under normal conditions, the voltage across the open terminals is zero. During a ground fault, a voltage will appear across these terminals, which can be detected by a relay. All of these methods rely on detecting the imbalance caused by the ground fault, as there is no direct ground connection to measure the fault current.