Govur University Logo
--> --> --> -->
...

How do pressure reducing valves (PRVs) function within a high-rise sprinkler system and what are the testing and maintenance requirements?



Pressure reducing valves (PRVs) are crucial components in high-rise sprinkler systems because they regulate water pressure to prevent over-pressurization of the sprinkler heads and piping on the lower floors. In a high-rise building, the static pressure from the water supply increases with elevation. Without PRVs, the pressure at the lower levels could exceed the maximum operating pressure of the sprinkler heads and piping, leading to leaks, damage, or even system failure. PRVs are installed at strategic locations throughout the sprinkler system to reduce the pressure to an acceptable level. They automatically adjust to maintain a constant downstream pressure, regardless of fluctuations in the upstream pressure. The PRV functions by using a diaphragm or piston that responds to the pressure differential between the inlet and outlet sides of the valve. When the outlet pressure exceeds the setpoint, the diaphragm or piston moves to restrict the flow of water, reducing the downstream pressure. When the outlet pressure drops below the setpoint, the diaphragm or piston moves to increase the flow of water, raising the downstream pressure. The testing and maintenance requirements for PRVs are essential to ensure their proper operation. PRVs should be visually inspected regularly to check for any signs of damage, leaks, or corrosion. The inlet and outlet pressures should be measured to verify that the valve is maintaining the correct downstream pressure. The PRVs should be exercised periodically by fully opening and closing them to prevent them from becoming stuck or clogged. A full flow test should be conducted annually to verify that the PRV can deliver the required flow rate at the design pressure. The PRV should be disassembled and inspected internally every five years, or more frequently if necessary, to check for wear, damage, or corrosion. Any worn or damaged parts should be replaced. The PRV should be re-calibrated after maintenance or repairs to ensure that it is maintaining the correct downstream pressure. All inspections, tests, and maintenance activities should be documented in a report. By following these testing and maintenance requirements, the reliability and effectiveness of PRVs in high-rise sprinkler systems can be ensured, providing adequate fire protection without over-pressurizing the system.