What are the key considerations when specifying a backflow prevention assembly for an irrigation system connected to a potable water supply to safeguard against contamination?



When specifying a backflow prevention assembly for an irrigation system connected to a potable water supply, several key considerations are crucial to effectively safeguard against contamination of the drinking water. A backflow prevention assembly is a device designed to prevent the reverse flow of water from the irrigation system back into the potable water supply. This reverse flow, known as backflow, can occur due to backpressure or backsiphonage, and can introduce contaminants from the irrigation system (e.g., fertilizers, pesticides, bacteria) into the drinking water. The primary considerations are as follows: 1. Degree of Hazard: The level of protection required depends on the potential hazard level. Irrigation systems are generally considered a high hazard because they handle substances that could be harmful if introduced into the potable water supply. Therefore, a high-hazard backflow preventer is typically required. 2. Type of Backflow Preventer: The most common types of backflow preventers for high-hazard applications are Reduced Pressure Principle (RP) assemblies and Pressure Vacuum Breakers (PVB). RP assemblies provide the highest level of protection, using two independently acting check valves and a pressure-regulated zone between them. If either check valve fails, the pressure in the zone drops, causing a relief valve to open and discharge water, preventing backflow. PVBs are simpler and less expensive but must be installed at least 12 inches above the highest point of the irrigation system to prevent backsiphonage. They are not suitable for all applications. 3. Local Codes and Regulations: Local plumbing codes and water purveyor regulations dictate the specific type of backflow preventer required and the installation requirements. Compliance with these regulations is mandatory. 4. Size and Flow Capacity: The backflow preventer must be sized appropriately for the flow rate of the irrigation system. Undersized preventers will cause excessive pressure loss and reduced system performance, while oversized preventers may not operate properly at low flow rates. 5. Installation Requirements: Backflow preventers must be installed in accordance with the manufacturer's instructions and local codes. This includes proper orientation, accessibility for testing and maintenance, and protection from freezing. 6. Testing and Maintenance: Backflow preventers require periodic testing to ensure they are functioning properly. Local codes typically specify the frequency of testing (e.g., annually) and require that testing be performed by a certified backflow tester. Regular maintenance, such as cleaning and lubrication, is also essential to maintain the preventer's performance. 7. Environmental Conditions: The backflow preventer must be suitable for the environmental conditions in which it will be installed. This includes temperature extremes, exposure to sunlight, and potential for vandalism. 8. Material Compatibility: The materials used in the backflow preventer must be compatible with the water quality and any chemicals that may be injected into the irrigation system. By carefully considering these factors, you can specify a backflow prevention assembly that effectively protects the potable water supply from contamination and ensures the safe operation of the irrigation system.